APC 120V 30A Rack Mounted PDU - Refurbished, Used and New
APC 120V 30A rack PDUs feed a full rack of switches, servers and storage from one NEMA L5-30P twist-lock circuit, with a 24A continuous load rating that a 15A or 20A strip cannot match. Most models in this collection are zero U vertical strips with 24 NEMA 5-20R outlets that mount in the rear channel of the rack without using any rack units, and one is a 2U horizontal unit with 16 outlets for racks that have no vertical mounting space. The collection spans basic, metered and switched types, and both the original AP75xx/AP79xx generation and the later AP88xx/AP89xx generation. NetworkTigers sells these PDUs refurbished, used and new, and every unit is tested before it ships so it works when it arrives.
APC 120V 30A rack PDU models
| Model | Type, outlets and form factor | Shop |
|---|---|---|
| AP7532 | Basic: 24x NEMA 5-20R, zero U vertical, L5-30P input, no network port, straight power distribution | AP7532 |
| AP8832 | Metered: 24x NEMA 5-20R, zero U vertical, L5-30P input, later generation with local current display and network monitoring | AP8832 |
| AP7932 | Switched: 24x NEMA 5-20R, zero U vertical, L5-30P input, original generation with per-outlet on/off over the network | AP7932 |
| AP8932 | Switched: 24x NEMA 5-20R, zero U vertical, L5-30P input, later generation with per-outlet on/off and updated network management | AP8932 |
| AP7902 | Switched: 16x NEMA 5-20R, 2U horizontal, L5-30P input, for racks without a vertical PDU channel | AP7902 |
| Later-generation 30A units | All AP88 and AP89 series metered and switched units on the page | AP88 metered | AP89 switched |
| Related APC | Other APC rack PDU collections by voltage and amperage | All 120V PDUs | 120V 20A | 120V 15A | 208V PDUs | All APC PDUs |
Which 120V 30A rack PDU do I need?
- Check the receptacle. Every PDU here plugs into a NEMA L5-30 twist-lock outlet. If the rack is fed by a straight-blade 5-15 or 5-20 outlet, you need the 15A or 20A collection instead.
- Add up the load. A 30A circuit is rated for 24A continuous, about 2.8 kW at 120V. Sum the nameplate draw of the equipment, and leave headroom for the inrush when everything powers on at once.
- Pick the control level. Basic (AP7532) for a closet nobody needs to monitor, metered (AP8832) when you want to see the load and get alarms before a breaker trips, switched (AP7932, AP8932, AP7902) when you need to reboot a device remotely or stagger outlet power-up.
- Pick the form factor. Zero U vertical strips need a rear PDU channel or mounting pegs in the rack; the AP7902 takes 2U of rail space instead.
- Match outlet count to plugs. All 24 or 16 outlets are 5-20R, which accept both 5-15P and 5-20P equipment cords.
Frequently asked questions
What changed between the AP7932 and the AP8932?
Both are switched zero U strips with 24 NEMA 5-20R outlets and an L5-30P input. The AP8932 is the later generation, with a newer network management platform, a different display and an updated chassis. If you already run AP79xx units and want spares that match, the AP7932 is the like-for-like choice; for a new rack, the AP8932 gives you the current firmware line.
Can I daisy-chain two 30A PDUs on one circuit?
No. Each PDU should have its own L5-30 circuit. Putting two 24-outlet strips on one 30A feed only makes sense if the total load is well under 24A, and it defeats the point of the second strip, which is usually to give each server a feed from a separate circuit or UPS.
Do the metered and switched models need a separate management card?
No. The network management on these units is built in. Connect the Ethernet port, set an IP address, and reach the unit by web browser, SNMP or command line.
NetworkTigers has sold enterprise network equipment since 1996. Every PDU carries the NetworkTigers 365-day warranty. Outfitting a row of racks? Ask us for a quote.